Table of Contents
Constant Watt Heating Cable MIQ™
MIQ high performance mineral insulated heating cables are used extensively for high temperature maintenance, high temperature exposure and/or high watt density applications which exceed the limitations of thermoplastic insulated cables. The resistance configurations available can provide tracing for pipes up to 1.6 km (1 mile) long from a single power supply point.
Constant Watt Heating Cable MIQ mineral insulated cables are manufactured using Alloy 825, a high nickel/chromium alloy ideally suited for high temperature service that offers exceptional resistance to stress corrosion in chloride, acid, salt and alkaline environments.

RATINGS
Rated voltage 1 ………………………………..300 and 600 Vac
Max. maintenance temperature 2 …………..932°F (500°C)
Max. continuous exposure temperature
Power-off……………………………………..1,112°F (600°C)
Max. watt density 2………………….. up to 80 w/ft (262 w/m)
Minimum installation temperature…………… -76°F (-60°C)
Minimum bend radius ………………………….. 6 x cable O.D

CONSTRUCTION
1 Solid alloy or copper conductor(s)
2 Compacted magnesium oxide insulation
3 Seamless alloy 825 sheath
MIQ HEATER SETS
Thermon MIQ cable sets are available in four factory fabricated configurations: Type A, B, D or E. The standard assemblies consist of a predetermined length of heating cable joined to a standard 4’ (1.2 m) or 7’ (2.1 m) nonheating cold lead with 12” (305 mm) long thermoplastic insulated pigtails.
The nonheating section of the unit is sealed and fitted with a high pressure, liquid-tight 1/2” or 3/4” NPT stainless steel gland 3 for connection into the supply junction box.

Datasheet: Constant Watt Heating Cable MIQ™
Contact
- Email: Hung.tran@wili.com.vn
- WhatAPP: 0903710753