Table of Contents
Self-Regulating Heating Cable KSX™
High performance Self-Regulating Heating Cable KSX are designed specifically for high heat loss freeze protection applications or process temperature maintenance where steam cleaning is not required.
The heat output of KSX varies in response to the surrounding temperature by reducing its thermal
output with increasing temperature.
KSX is certified for use in ordinary (nonclassified) areas and in potentially explosive atmospheres in accordance with the ATEX Directive and the IECEx Scheme.
RATINGS
Available watt densities …..15, 32, 48, 64 W/m @ 10°C
Nominal supply voltages 1…………………………………..230 Vac
Max. maintenance or exposure temperature
Continuous power-on……………………………………………121°C
Minimum installation temperature ……………………-60°C
Minimum bend radius
@ -15°C……………………………………………………………………..10 mm
@ -60°C……………………………………………………………………32 mm
T-rating based on stabilized design 2 …………….T3 to T6
CONSTRUCTION
1 Nickel-plated copper bus wires (1.3 mm2)
2 Semiconductive heating matrix and fluoropolymer dielectric insulation
3 Tinned copper braid
4 Fluoropolymer overjacket provides additional protection to core, insulation, and braid where
exposure to chemicals or corrosives is expected.
BASIC ACCESSORIES
Thermon offers system accessories designed specifically for rapid, trouble-free installation of
Thermon heat tracing.
All trace heaters require a connection kit to comply with approval requirements.
Datasheet: Self-Regulating Heating Cable KSX™
Contact
- Email: Hung.tran@wili.com.vn
- WhatAPP: 0903710753