Table of Contents
Self-Regulating Heating Cable DSX™
Self-Regulating Heating Cable DSX is a robust and optimized solution for the freeze protection of small and medium diameter industrial piping systems. The trace heaters self-regulate to prevent overheating, even when overlapped, and are marked for use in ordinary and hazardous locations.
DSX™ offers 9 and 18 W/m nominal power outputs and can be energized from 208 to 277 Vac. Product construction options include polyolefin or fluoropolymer overjacket and braid or foil and drain wire electrically conductive covering. Specify DSX™ today for a safe, easy to install, and energy efficient freeze protection solution in an optimized form factor.
EASY TO INSTALL
Parallel circuitry allows DSX to be cut to suit any length required in the field. Flexible materials and small cross-section provide an excellent bending radius for wrapping around complex geometries.
ENERGY EFFICIENT
The heat output of DSX varies along the length of the traced equipment or surface, providing the optimal heating for colder or warmer spots.
As the temperature drops, heat output increases.
Conversely, when the temperature increases, heat output decreases
SAFE
DSX self-regulates to prevent overheating, even when overlapped. Trace heaters are marked for ordinary (non-classified) areas and in potentially explosive atmospheres in accordance with the ATEX Directive and the IECEx Scheme.
RELIABLE
Built with proven and proprietary compounding, extrusion, and cross-linking technology, DSX allows for continuous operation and extended life expectancy.
RATINGS
Available Watt densities ……………………………………………………… 9, 18 W/m at 10°C and 230 Vac
Nominal supply voltage range ……………….208–277 Vac
Maximum maintenance temperature… 65°C (149°F)
Maximum continuous exposure temperature
Power-off……………………………………………………….85°C (185°F)
Minimum installation temperature ……. -60°C (-76°F)
Minimum bend radius
@ -15°C (59°F)…………………………………………….10 mm (3/8”)
@ -60°C (-76°F)……………………………………….32 mm (1-1/4”)
T-Rating 1
9, 18 W/m……………………………………………………………. T6/T85°C
CONSTRUCTION
- Nickel-plated copper bus wires 0.6 mm2
(20 AWG)
2.E-Beam cross-linked semiconductive heating
matrix - E-Beam cross-linked dielectric insulation
4.Tinned copper braid - Polyolefin overjacket provides additional
protection to core, insulation, and braid where
exposure to aqueous inorganic chemicals is
expected.
Datasheet: Self-Regulating Heating Cable DSX™
Contact
- Email: Hung.tran@wili.com.vn
- WhatAPP: 0903710753