Heat Trace Thermon, Self-Regulating Heat Cable

Self-Regulating Heating Cable DLX™ Sales agent VietNam, Laos, Cambodia

Self-Regulating Heating Cable DLX™

Self-Regulating Heating Cable DLX is a robust and optimized solution for the freeze protection of small and medium diameter commercial piping systems. These cut-to-length trace heaters self-regulate to prevent overheating, providing an easy-to-install and energy efficient solution.

DLX™ offers 10 and 20 W/m nominal power outputs and can be energized from 100-120 or 208-277 Vac. Choose between braid or foil and drain wire options, with a UV and abrasion-resistant polyolefin jacket. Specify DLX™ today for a safe, easy to install, and energy efficient freeze protection solution in an optimized form factor.

Self-Regulating Heating Cable DLX™ Sales agent VietNam, Laos, Cambodia
Self-Regulating Heating Cable DLX™ Sales agent VietNam, Laos, Cambodia

EASY TO INSTALL
Parallel circuitry allows DLX to be cut to suit any length required in the field. Flexible materials and small cross-section provide an excellent bending radius for wrapping around complex geometries.

ENERGY EFFICIENT
The heat output of DLX varies along the length of the traced equipment or surface, providing the optimal heating for colder or warmer spots. As the temperature drops, heat output increases.
Conversely, when the temperature increases, heat output decreases

SAFE
DLX self-regulates to prevent overheating, even when overlapped. Trace heaters are certified for ordinary (non-classified) areas.

RELIABLE
Built with proven and proprietary compounding, extrusion, and cross-linking technology, DLX allows for continuous operation and extended life

RATINGS

Available Watt densities ……….10, 20 W/m (3,6 W/ft) at 10°C (50°F)
Nominal supply voltage 1 …….100-120 or 208-277 Vac
Maximum maintenance temperature… 65°C (149°F)
Maximum continuous exposure temperature
Power-off……………………………………………………….85°C (185°F)
Minimum installation temperature ……. -60°C (-76°F)
Minimum bend radius
@ -15°C (59°F)…………………………………………….10 mm (3/8”)
@ -60°C (-76°F)……………………………………….32 mm (1-1/4”)

CONSTRUCTION

  1. Nickel-plated copper bus wires 0.6 mm2
    (20 AWG)
    2.E-Beam cross-linked semiconductive heating
    matrix
  2. E-Beam cross-linked dielectric insulation
    4.Tinned copper braid
  3. Polyolefin overjacket provides additional
    protection to core, insulation, and braid where
    exposure to aqueous inorganic chemicals is
    expected.

Datasheet: Self-Regulating Heating Cable DLX™