Self-Regulating Heat Cable BSX™
These top of the line heating cables provide both freeze protection and process temperature maintenance for metallic piping as well as non-metallic piping, tanks and equipment. The heat output of the cable is designed to change in response to the conditions along the entire circuit. When the heat loss of the equipment increases, the heat output of the cable increases. When the heat output decreases as ambient temperature rises, the cable output will decrease as well.
Self-Regulating Heat Cable BSX™ is certified for use in ordinary areas and in potentially explosive atmospheres. The cable is easy to maintain and does not require steam cleaning.
RATINGS
Available watt densities ………..10, 16, 26, 33 W/m @ 10°C
(3, 5, 8, 10 W/ft @ 50°F)
Supply voltages ……………………………..110-120 or 208-277 Vac
Max. maintenance temperature………………… 65°C (150°F)
Max. continuous exposure temperature
Power-off…………………………………………………………..85°C (185°F)
Minimum installation temperature ………… -51°C (-60°F)
Minimum bend radius
@ -15°C (5°F)………………………………………………..10 mm (0.38”)
@ -60°C (-76°F)…………………………………………… 32 mm (1.25”)
T-rating 1
10, 16, 26 W/m (3, 5, 8 W/ft)…………………..T6 85°C (185°F)
33 W/m (10 W/ft)…………………………………….T5 100°C (212°F)
CONSTRUCTION
1 Nickel-plated copper bus wires (16 AWG)
2 Radiation cross-linked semiconductive heating
matrix
3 Radiation cross-linked dielectric insulation
4 Tinned copper braid
5 Polyolefin overjacket provides additional
protection for cable and braid where exposure to
aqueous inorganic chemicals is expected.